Cold Weather Operating Problems with SF6 Circuit Breakers

IEEE Standards

ANSI/IEEE C37.04-19791 and ANSI/IEEE C37.010-19792 are the standards relating to the rating structure and application of circuit breakers. There is no specific advice concerning low temperature. The standard service conditions are covered in C37.041, which includes altitude less than 1000m, and a temperature range of -30°C to +40°C. Other features are covered as well, from seismic to frequency. There is reference in C37.04.2.3.31 to low temperature as an unusual operating condition. And -60°C certainly is unusual.

SF6 Circuit Breakers and SF6 Basics

SF6 has unique properties which render SF6 a nearly ideal media for arc interruption and dielectric strength. The dielectric strength is greater than any other known media at the same density. The reason lies in the relatively large physical size and mass. The molecular weight is 146. Nitrogen and Oxygen are 28 and 32 respectively. The size and mass help reduce the propagation of free electrons. SF6 also acts as an inelastic damper for collision mechanism. SF6 is in the same class as freons which all have excellent dielectric properties. SF6 has unusual thermal properties which contribute to its arc interruption. SF6 has intrinsically higher thermal conductivity at low temperatures. Figure 1, which is a plot of the thermal conductivity in Watts/cm2/K° of SF6 and N2 and temperature. The existence of this peak in conductivity results from a change of state of the gas. The disassociation requires a well defined amount of energy, much like the heat of vaporization. This enhances the thermal transfer at arc, helping reduce the arc temperature. Conversely in lower ambient the elements recombine and liberate this energy, transporting copious amounts of energy across the electric arc.

Figure 1


In other diatomic gases like O2 and N2, SF6 becomes conductive when ionized. SF6 remains basically an insulator during the disassociation of the arc, further aiding the dielectric and interruptive properties. The disassociation of SF6 produces Fluorine, the most electronegative element, at 3.95, in the periodic chart (Figure 2). This enhances the capture of free ions, and capturing free ions reduces conductivity. As the temperature of the arc is reduced, Fluorine ions, with less than 1 percent the mean free velocity of electrons, capture free electrons and reduce the current density significantly. These two properties, high electro-negativity which results in high electron capture, and high thermal conductivity at relatively low temperatures, give SF6 its ‘made for electrical apparatus’ properties.


Figure 2


Although the gas is nearly ideal, it does have one major disadvantage. The main disadvantage, from our perspective, is the relatively high liquefaction point of SF6. Figure 3 The liquefaction occurs between -10°F and -30°F, depending on the density (70psig to 95psig ranges found in circuit breakers manufactured today3) of the SF6. Here we have somewhat conflicting requirements; the need to extinguish the arc and provide dielectric strength, and the physics of SF6. The higher densities and pressures increase the liquefaction temperature, a very unsatisfactory side effect. In locations where the wintertime temperatures fall below -10°F, for even an overnight excursion, the manufacturer or user must provide supplement means to maintain the SF6 above -10°F. Figure 4 Sometimes the choice is made to maintain the gas warmer to allow a prudent reserve heat mass as a safety margin.

Figure 3

Figure 4

Cold Weather Testing

Reflecting on our operational experience, it would appear that cold weather testing to date does not adequately reflect environmental conditions. In many cases, Minnesota Power and other northern climate electric utilities have provided the test laboratories for cold weather.

Operating History With SF6 Circuit Breakers

Minnesota Power has in service 90 SF6 circuit breakers from five separate vendors. Additionally, these five vendors have supplied Minnesota Power with several models and voltage classes. If all are considered different ‘types,’ there are about ten on the Minnesota Power system. Invariably, there has been a wide range of operating experience, however all have performed adequately, albeit varying levels of maintenance.

Incidents in February 1996

The normal learning curve for this apparatus and problems associated with all the various styles are manageable, taken during the normal course of maintenance. Operations and Maintenance help to clarify the situation and the problems are remedied on a regular basis. Even with a few alarms on an overnight temperature sag, after operators gain experience with the thermal recovery of the tanks and density monitors, the situation is tractable. However, in the period January 19 through February 2 our service territory experienced temperatures in excess of -50ºC and several nights the temperature sagged to near -60°C. On the morning of February 2, MP had 22 SF6 circuit breakers in alarm and three, 134L, 115MW and 762L, were locked out. The three that were locked out were all at the International Falls 115/15kV Substation. International Falls experienced -45°C that morning with a wind chill of -80°C. MP has produced composite charts from U.S. Weather Service data (5) of air temperature, average wind speed and nominal wind drill for three locations in our service territory (see Figure 5).

Figure 5


This station provides service to International Falls, Boise Cascade and the surrounding area, and is the interconnection with Ontario Hydro at Fort Frances. Any event which causes a transfer trip or breaker failure and cannot be cleared at the site has serious consequences to customers. MP serves International Falls and several smaller communities from this substation, as well as several major customers. An outage at this time of the winter is very undesirable. A disturbance on the line could have meant breaker operations at Little Fork/Running 230kV Substation. MP is relying at Little Fork 230kV Substation, as well, for SF6 breakers to operate.

To bring the International Falls substation back into service would have posed severe hardships. All systems, because of the extremely low ambient and wind chill, would cool quickly. Maintaining heat in the control house would have been difficult. At temperatures below 45°F, the capacity of lead acid batteries is reduced significantly from the nominal 77°F. IEEE C57.12.00-19934 section 4.1.2.2 and 4.1.2.3 outline the standard operating and design conditions for transformers, and top oil temperatures or starting temperatures below -20°C (-4°F) are not considered usual operating conditions. Unless specified and designed to meet the lower starting temperatures, there may be restrictions on operating and loading the transformer. During this period, Duluth experienced 13 days in a row where the minimum temperature was -10°F (-23.3°C) to -39°F (-39.4°C)5. What is the best means to start a transformer at these temperatures? Many of the vendors recommend heating the core and coils. At the time of this event, MP was not prepared for this scenario. MP does have procedures in place for supplement heating should such an event occur.



Cold Climate Problems

Heaters The existing heaters on many of the early designs were insufficient for a number of reasons. MP has changed or added heaters on approximately 25 SF6 circuit breakers.
Density Monitors These presented another problem. Initial settings were incorrect. These devices also proved to be very difficult to set accurately and repeatability was a problem.
Sealing First generation of SF6 circuit breakers Minnesota Power has in service also have leaking problems in cold weather.
SF6 Plumbing Vendors have designed the SF6 fill and instrument lines on the circuit breakers to minimize cost and present a neat appearance, both of which are contrary to successful operation in cold weather. Usually, the design routes the piping neatly around supports to the control housing. Additionally, unless specified otherwise, the vendor uses smaller diameter flow lines. All the bends, restrictions and low spots add areas for condensation. The length and turns increase the fill and evacuation times of the tank. The low spots and length worsen the low temperature problem. More surface area is added and the low spots help the SF6 condense, and the smaller diameter leaves less thermal mass of SF6.
Station Service Many of the SF6 circuit breakers were added to existing substations. The replacement of a single circuit breaker usually doesn’t warrant the close examination of the station service. Existing oil circuit breakers have, however, minimal heating requirements and, as a whole, their AC load is not significant. Some designs of SF6 circuit breakers have as much as 5kW to 7kW of connected load. In the case where several have been changed the upgrade of the station service probably may have been undertaken. In the situation where one per year is changed in a station, this has been frequently overlooked. Not only has the effect on the station service been missed, proper branch circuit sizing has been neglected. In several cases the effect has been as much as a 10 percent reduction in voltage at the breaker. The result is as much as a 20 percent reduction in wattage to the tank heaters. This results in further compromising the tank heating system. Unfortunately this condition was at the International Falls substation. In this case the circuit breakers were new but the AC branch circuit was undersized.


Solutions

Operation

We began seriously to consider the effects of a failure to operate and failure of a breaker. We quickly realized that, as the breaker approached the magic alarm set point, the functionality of the circuit breaker didn’t vanish. Rather, under reduced gas pressure, the capacity of a circuit breaker to interrupt is diminished and a likewise similar condition for the dielectric strength. In reality, at lockout the interrupting capacity on our 115kV class of circuit breaker was reduced about 10 percent 6. The SF6 breaker vendors of Minnesota Power indicate that their circuit breakers can withstand system voltage at 15psig7, and in some cases interrupt load current. Minnesota Power has procured exclusively 40kA circuit breakers over the years. At 10 percent reduction in interrupting capacity there still remains adequate margin, except at a few sites.

We investigated the failure mechanism of SF6 circuit breakers. The vendors were not excited to discuss this condition. Apparently, there has not been any factory testing to simulate this event or anything similar. And most likely, failures have not been communicated to the vendors. The case we proposed was a breaker with a gross breach of the tank so the gas pressure was 15psig. Our concern was not for the final condition of the breaker but the failure mode. We were concerned about the self destruction of the tanks. Violent damage to the tank or porcelain could damage nearby apparatus or harm nearby workers. We were not able to learn of any catastrophic or eruptive failures of the designs in service at Minnesota Power. The worst case we uncovered was a utility operating, under load, a SF6 circuit breaker with nearly atmospheric pressure in the tank. In this case there was a complete burn through of the tank wall.

Minnesota Power does not envision operating, and has not operated, breakers in this condition. However, we do plan to utilize fully the circuit breaker capacity to avert a possibly more harmful situation. We are willing to assume the risk of breaker damage or self destruction. Minnesota Power is prepared for damage to a circuit breaker if necessary to protect apparatus or reduce the risk of a more extensive outage. We are actively investigating means and methods to avoid this situation. We believe a greater risk exists in having inoperable circuit breakers during such an event. Warrantee claims were not a consideration.

Physical Changes

Remove Block On live tank circuit breaker at strategic locations we have disabled the block for tripping. The breaker still has alarms, but we do not inhibit tripping.
Temperature Recovery Simply wait for the circuit breaker SF6 gas to recover after the temperature excursion. Normally, the temperature will recover sufficiently in two to four hours to reverse the alarm or lockout condition. This is the operating tactic that has been employed in the past successfully. Eventually, with other modifications we hope to eliminate this scenario.
Gas Mixtures On live tank circuit breakers the remedial options to extend cold weather operation are few. The only option of which we are aware is to use a gas mix of SF6 and CH4. This is not an acceptable option for us. Mixing creates its own set of problems.
Retrofit Density Monitors This was done initially on ten 115kV dead tank circuit breakers. MP worked closely with the vendor to install new or recalibrated density monitors. One problem we suspected was that confusion with Fahrenheit versus Centigrade occurred on the factory settings. A second problem was the repeatability of certain devices. All of these issues have been resolved.
Heaters Part of the solution was to increase the heater size on many of the circuit breakers. There was insufficient heater wattage for our application and climate.


Ongoing Problems

Seals, No Solutions The cold weather and temperature extremes aggravate the operability of SF6 circuit breakers. A few first generation, two pressure SF6 circuit breakers have soldered connections on the bushings. The thermal cycling from -45°C to +35°C in our service area we believe is the chief cause. Minnesota Power has no unique solution for this situation. In the case that affects six 230kV older design two pressure SF6 circuit breakers, we are replacing them over a three year period.


Innovative Solutions

After the events described above, Minnesota Power embarked on a more aggressive course to correct the deficiencies. We have addressed the problem in two ways; one to prevent the reoccurrence of this situation and to repair and retrofit existing sites. The prevention is simply the institution of tighter specifications and closer monitoring of the breaker vendors and the closer examination of AC branch circuits and station service, as well. Secondly, we have redesigned the entire temperature control system.

Minnesota Power has designed and optimized a retrofit temperature control system - Breaker Blankit - for existing circuit breakers. The design consists of new silicon rubber tank heaters, optimized PID control thermostat, tank insulation and SF6 flow line insulation (Figure 6). This system has the potential to solve many of the problems described above. The system should eliminate nuisance low pressure alarms, so that no false positive are received at the Minnesota Power Control Center. Maintenance forces can concentrate on real, not virtual, problems. Secondly, because we maintain temperature better, we are assured that, in fact, the breaker has the capacity on the nameplate. No derating or compromise in the ratings are necessary. Third, the system should reduce long term maintenance because the components are chosen for a 20 year life minimum. Fourth, with this system there is a potential for energy savings for each breaker. This can be significant in some breaker designs.


Figure 6

System Design Parameters

Objectives

Material

The heater is silicone rubber design, presently in use by OEM breaker vendors. The heater is designed with a very low watt density less than 2 watts/in2. In discussion with the supplier of the heating system, the threshold value to assure 20 operations of the heater was a maximum of 2.5 watts/in.26.

The insulation system is Teflon coated fiberglass fabric and Teflon impregnated fiberglass, custom designed and fabricated to various vendor tank designs. The material fabric and insulation have been used for 20 years in the petrochemical industry.

The controls are manufactured as a complete system with PID controller with optional heater circuit continuity annunciation. Heater control is a type K thermostat mounted on the center phase. Each heater element is protected by an over temperature relay.

Results

Installations The system is installed at 10 sites at Minnesota Power, 20 circuit breakers total. These 20 circuit breakers include models from three vendors. One installation is at an adjacent utility.
Alarms and Lockouts Although the winter of 1996-1997 was milder than 1995-1996, Minnesota Power experienced no alarms from any of the retrofitted breakers.
Test Site The Minnesota Power Virginia 115/69/46kV Substation was selected as a test site for the new system. This is geographically near the center of the Minnesota Power service territory and can be reasonably expected to experience system average temperatures.
Temperature The temperature is being monitored on two Minnesota Power breakers, nearly identical HVB™ 121kV, 2000 ampere 25L and 16L, serial numbers, h121a2058-205 and h121a2058-207, respectively. 16L breaker was the control breaker and the 25L had the Breaker Blankit™ system installed. The temperature is being collected with an Omega™ data logger that has the capability to be remotely downloaded. In this case, we are manually retrieving data from the unit. This unit has about 90 days available for storage. The installation was in place February 23, 1997, but not in time to collect any meaningful data from the winter. Minnesota Power will continue to monitor the test site throughout this winter.
Power Usage Both circuit breakers are metered with identical single phase watt-hour meters. These are nominally used for residential metering on MP's system. Potential is taken from the existing AC power supply to the breaker. Clamp on type current transformers are used on the tank heater circuit. We expect the results to show a significant reduction in power use from our control breaker. Initially, the heaters are sized with respect to the insulation which provides a high insulating factor. The heaters sized this way are 80 to 85 percent of the original.
 

The objective is to show that the heat maintenance system provides four benefits:

  1. More uniform circuit breaker tank temperatures.
  2. Less total heat required to maintain SF6 at optimal temperatures.
  3. Eliminate all nuisance alarms.
  4. Provide longer term operating history to satisfy that system does not deteriorate breaker performance in any manner.

Summary

Severe cold climates can pose problems for utilities operating SF6 circuit breakers. The problems can range from nuisance alarms to lockouts and actual loss of gas. Minnesota Power has battled successfully the elements for several years when operating SF6 circuit breakers. The prevailing attitude has been to accept the wintertime problems as just part of the learning curve and the way it is. The experience of the winter of 1996 has taught Minnesota Power that the problems, under unfortunate circumstances, can pose much greater difficulties. To address our problems, Minnesota Power has designed a retrofit kit that is being added to all our circuit breakers, which we hope is a permanent solution to cold weather operating problems. The product has been installed on twenty (20) 115kV and 230kV circuit breakers, to date, on our system and one on a neighboring utility. The first installation was completed in October 1996 at International Falls. To date, the results have been favorable, with no alarms on any of the 20 installations throughout the winter. A complete test site was installed in February 1997 to monitor the supplemental breaker heating system. Testing is continuing to determine actual energy savings from their use, any other unforeseen long term effects and the real time performance during extreme temperature excursions.


References

ANSI/IEEE C37.04-1979 - IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis


  1. ANSI/IEEE C37.010-1979 - IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis

  2. SF6 Switchgear, H. M. Ryan and G. R. Jones, Peregrinus Press, 1989

  3. IEEE C57.12.00-1993 - IEEE Standard General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformers

  4. U.S. Weather Service, Duluth, MN

  5. Watlow Electric Manufacturing, St. Louis, MO

  6. N I Supply, Hermantown, MN

[Back to Breaker Blankit]
[Back to APS Main]
[Back to Metatech Main]

Updated 1/20/2000